地下室上浮開裂事故的鑒定與加固處理
徐春國
- 摘 要
-
徐春國
(廣東省佛山市建筑工程質(zhì)量監(jiān)督站 528000)[提要] 某大廈地下室受地下水浮力作用不均勻上浮(最大上浮值213mm),造成地下室梁、柱出現(xiàn)寬度達(dá)1.0~2.5mm的裂縫,結(jié)構(gòu)處于極限破壞狀態(tài)。針對該工程分析了事故產(chǎn)生的原因,介紹了利用巖土錨桿對地下室結(jié)構(gòu)進(jìn)行抗浮加固處理的方法。
[關(guān)鍵詞] 地下室 抗拔力 浮力 鋪桿A building's basement rose up at Foshan city because of groundwater buoyant force action, maximum springing deflection was 213mm, which caused l.0~2.5mm width cracks on the beams and columns of the basement.The structure was in limit state.The cause of the accident is analyzed. The reinforcing treatment for the basement by anchor bars is also introduced here.
Keywords: basement; pulling resistance force; buoyant force; anchor bar